Thermal Circuit Breakers
1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic recovery
5.Voltage display(voltage measurement)
6.Current display (current measurement)
7. Voltage calibration: Voltage +-10% adjustable. A13
8. Restore factory : press the down button for more than 12s
9.Fault inquiry: Press the UP button from more than 12S
1.Model number:TOVPD1-100-EC
2.Power supply:220VAC 50/60Hz
3.Max.Loading power:100A
4.Over-voltage protection value range:230V~300~OFF(default:270V)
Over-voltage recovery voltage range:225V--295V(default:250V)
Over-voltage protection action time:0.1s~30s(default value:0.5s)
Over-voltage recovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:140V--210V --OFF(default:170V)
Under-voltage recovery voltage range:145V--215V (default:190V)
Under-voltage protection action time:0.1s~30s(default:0.5s)
Under-voltage recovery delay time:1s~500s(default:30s)
6.Over-curren